Analog converters:
EZ-SG: |
|
Strain gauge to DC isolator / converter |
EZ102: |
|
Potentiometric to DC isolator / converter |
EZ109REG: |
|
Universal converter with galvanic isolation |
EZ109REG2: |
|
High performance universal converter |
EZ109REG2-H: |
|
High performance universal converter, 85-265 V |
EZ109S: |
|
DC current isolator |
EZ109UI2: |
|
DC current / voltage converter |
EZ110D: |
|
DC current isolator (self-powered) double channel |
EZ110S: |
|
DC current isolator (self-powered) single channel |
EZ102
Potentiometric to DC isolator / converter
EZ102 accepts signal from rheostat (2 wires) or potentiometer (3 wires) and converts/isolates it into mA/V standard signals. The auxiliary power supply allows also an active or passive connections on the output side. A 3-way galvanic isolation among Power supply // input // output circuits assures the integrity of your datas.
Order code : |
|
EZ102 |
Description: |
|
Potentiometric to DC isolator / converter |
Input: |
|
2 wire rheostat, 0..300/500, 0..1000 Ω, 3 wire potentiometer, 200 Ω..1 MΩ |
Output: |
|
current 0/4..20 mA; voltage 0/1..5, 0/2..10 V |
Precision class: |
|
0,2% |
Power supply: |
|
19..40 Vdc, 19..28 Vac |
Isolation: |
|
1.500 Vac |
EZ109REG
Analog universal converter with galvanic isolation
EZ109REG is an universal converter for analog input: voltage, current, thermocouples, PT100, potentiometer. EZ109REG assures sensor powered by 2-wire technique: 20Vcc stabilised, 20mA max with short-circuit protection. The module guarantee measurement and re-transmission on isolated analog output, with voltage and current output. Type of input, zero and span, output mode (zero elevation, scale inversion), output voltage span (5 or 10 V) are settable by DIp-switch. By PC are settable: zero, span, square root extraction, filter, burn-out and other parameters.
Order code : |
|
EZ109REG |
Description: |
|
Analog universal converter with galvanic isolation |
Input: |
|
bipolar voltage up to 10 Vdc 4 scales, bipolar current up to 20 mA, thermoresistance (Pt100, 2/3 wires, -200..+600°C), thermocouple J,K,R,S,T,B,E,N, potentiometer (500 ohm..1,5 kohm) |
Output: |
|
current (0/4..20 mA), voltage (0..5/0..10/1..5/2..10 V) |
Precision: |
|
0,2% |
Power supply: |
|
19..40 Vdc, 19..28 Vac |
Isolation: |
|
1.500 Vac |
Programming: |
|
Dip-switch or software (Z-SETUP) |
EZ109REG-BP
Universal converter with bipolar mA / V output
EZ109REG-BP is a signal converter with universal input: voltage (mV), current (mA), thermocouples TC, thermoresistances RTD, potentiometer, rheostat, NTC. The module offers measurement and re-transmission on isolated analog bipolar output, with voltage output. By DIP-switch are selectable: type of input (start-end), output mode (zero elevation, scale inversion), output voltage type (mA or V). Through mini USB front connector, Z109REG-BP can be programmed by PC: start-end scale, additional input types, square root extraction, filter, burn-out etc.
Order code : |
|
EZ109REG-BP |
Description: |
|
Universal converter with bipolar mA / V output |
Power Supply: |
|
10..40 Vdc, 19..28 Vac |
Power transducer: |
|
Yes, 2-3 wire technique |
Isolation: |
|
1.500 Vac at 3 ways |
Input: |
|
Nr 1 channel |
Output: |
|
Nr 1 bipolar channel (±10 V, ±20 mA) |
Settings: |
|
Via software EASY SETUP / mini USB interface or DIP-switches |
Operating temperature: |
|
-20 – +65°C |
EZ109REG2-H
High performance universal converter, 85-265 V
EZ109REG2 is an advanced universal converter able to manage all analog signals (mA, V, PT100, Pt1000, Pt500, Ni100, TCs, Ohm) and convert / isolate it into mA/V standard signals. The device can be configured through dip-switches, PC software or handheld device. A digital contact is available as ALARM or STROBE (multiplexing). It can be requested with low or high power supply. A 3-way galvanic isolation among Power supply // input // output circuits assures the integrity of your datas.
Order code : |
|
EZ109REG2-H |
Description: |
|
High performance universal converter, 85-265 V |
Analog input: |
|
current up to 20 mA, voltage from 75 mV to 20 V, RTD (Pt100, Pt500, Pt1000, Ni100), thermocouple (J, K, R, S, T, B, E, N), potentiometer, rheostat |
Analog output: |
|
Current 0..20, 4..20 mA; voltage |
Digital I/O: |
|
Strobe Input / Relay output (SPST) |
Resolution: |
|
Programmable from 11 bit+sign to 15 bit+sign |
Precision class: |
|
0,1% |
Response time: |
|
35 ms (@11 bit+sign) |
Isolation: |
|
1.500 Vac |
Power supply: |
|
85..265 Vac/dc |
EZ109S
DC current isolator
EZ109S is a device that allows to isolate a mA signals. The device can power also all 2-wire sensors and it can be used to solve also power conflicts into the same mA loop. A 3-way galvanic isolation among Power supply // input // output circuits assures the integrity of your datas.
Order code : |
|
EZ109S |
Description: |
|
DC current isolator |
Input: |
|
Current 0..20, 4..20 mA, 20Vdc stabilized loop supply, input impedance 20 Ω |
Output: |
|
Current 0..20, 4..20 mA |
Response Time: |
|
<200 μs, cutoff frequency (-3dB) 6kHz |
Precision: |
|
0,2% |
Power supply: |
|
9..40 Vdc, 19..28 Vac |
Sensors supply: |
|
2 wires, 20 Vdc stabilized, 20 mA max protected against short circuit |
Isolation: |
|
1.500 Vac |
EZ109S-DI
Wide range Current Loop Isolator
The module EZ109S-DI is a power supply unit with galvanic isolator for the current loop. It converts an input signal into a current in the range 0/4..20mA and makes the measure and retransmission of the signal into an isolated analog output in the range 0/4 - 20 mA. The module can supply a 2-wire sensor with 20 V stabilized voltage and 20 mA maximum current short-circuit protected. The 3-way galvanic isolation reaches 3,500 Vac equivalent to 6.4 kV pulse voltage. Z109S-DI is very useful in energy sector applications.
Order code : |
|
EZ109S-DI |
Description: |
|
Wide range Current Loop Isolator |
Power Supply: |
|
10..40 Vdc, 19..28 Vac |
Input: |
|
0/4..20 mA, 20 Vdc stabilized loop suppyl, input impendance 50 Ω |
Output: |
|
Current 0/4..20 mA |
Response Time: |
|
< 200 μs, cutoff frequency (-3dB) 6kHz |
Isolation: |
|
3.500 Vac at 3 ways |
Safety isolation: |
|
< 300 V~ referred to ground CAT II |
Pulse Voltage: |
|
6,5 kV |
Power transducer: |
|
2-wire technique(max 20 mA) |
Dimension: |
|
100x 112 x 18 mm (l x h x w) |
Mounting: |
|
DIN rail 46277 |
Case: |
|
PBT, black |
EZ109UI2
DC current / voltage converter
EZ109UI2 is a device that accepts mA/V signals able to convert it into mA/V standard signals. It’s configurable either for monopolar or bipolar inputs and all parameters are configurable through dip-switches. The device can power also all 2-wire sensors. A 3-way galvanic isolation among Power supply // input // output circuits assures the integrity of your datas.
Order code : |
|
EZ109UI2 |
Description: |
|
DC current / voltage converter |
Input: |
|
voltage (9 scales, from 100 mV to 20 V), current (bipolar up to 20 mA) |
Re-transmitted output: |
|
voltage (0..10 / 2..10 V), current (0..20 / 4..20 mA) |
Accuracy: |
|
0,1% (current / voltage input) |
Sample frequency / resolution: |
|
from 240 sps (@ 11 bit + sign) up to 15 sps (@ 15 bit + sign) |
Power supply: |
|
9..40 Vdc, 19..28 Vac 50-60 Hz |
Power transducer: |
|
2 wire, 20 Vdc stabilized, 20 mA max protected against short circuit |
Isolation: |
|
1.500 @ 3 way |
Settings: |
|
DIP swich or jumper |
EZ110D
DC current isolator (self-powered) double channel
EZ110 is a 4..20mA isolator powered through the input loop. It does not require any auxiliary power supply. EZ110 is available in two different version: EZ110S (single channel) or EZ110D (double channel). A 2-way galvanic isolation between input // output circuits assures the integrity of your datas.
Order code : |
|
EZ110D |
Description: |
|
DC current isolator (self-powered) double channel |
Input: |
|
Current 4..20 mA |
Output: |
|
Current 4..20 mA |
Precision: |
|
0,1% |
Power supply: |
|
Self powered on input |
Isolation: |
|
1.500 Vac |
EZ110S
DC current isolator (self-powered) single channel
EZ110 is a 4..20mA isolator powered through the input loop. It does not require any auxiliary power supply. EZ110 is available in two different version: EZ110S (single channel) or EZ110D (double channel). A 2-way galvanic isolation between input // output circuits assures the integrity of your datas.
Order code : |
|
EZ110S |
Description: |
|
DC current isolator (self-powered) single channel |
Input: |
|
Current 4..20 mA |
Output: |
|
Current 4..20 mA |
Precision: |
|
0,1% |
Power supply: |
|
Self powered on input |
Isolation: |
|
1.500 Vac |
EZ170REG
DC duplicator / isolator with universal input and 2 output
EZ170REG allows to convert and duplicate an analog signal (mA, V, PT100, Pt1000, Pt500, Ni100, TCs, Ohm) by 2 indipendents outputs (mA or V). It disposes also of dip switches to set the available input/output ranges. The auxiliary power supply allows also an active or passive connections on the output side. A 4-way galvanic isolation among Power supply // input // output1 // output2 circuits assures the integrity of your datas.
Order code : |
|
EZ170REG |
Description: |
|
DC duplicator / isolator with universal input and 2 output |
Power Supply: |
|
10-40 Vdc; 19..28 Vac |
Power Transducer: |
|
Yes, current input (max 17 V) |
Isolation: |
|
1,5 kVac |
Input: |
|
Nr 1 channel, voltage range (0..10 V), current (0..20 mA) with active/passive connection, potentiometer (1..100 kΩ), thermocouple (J,K,R,S,T,B,E,N), thermoresistance (Pt100, Pt500, Pt1000, Ni100) |
Output: |
|
Nr 2 independent channel, voltage range (0..10 V); current (0..20 mA) with active/passive connection |
Accuracy: |
|
0,1% |
Operating temperature: |
|
-10..+65°C |
Dimension (wxhxd): |
|
100 x 112 x 17,5 mm |
EZ190
DC adder - subtracter / isolator
EZ190 allows to make the addition or the subtraction of 2 analog signal (mA or V) and get the equivalent output by an analog signal (mA or V). The two inputs can have also different importance. It disposes of dip switches to set the available input/output ranges. The auxiliary power supply allows also an active or passive connections on the output side. A 3-way galvanic isolation among Power supply // input // output circuits assures the integrity of your datas.
Order code : |
|
EZ190 |
Description: |
|
DC adder - subtracter / isolator |
Power supply: |
|
19..40 (9..30 option) Vdc, 19..28 Vac |
Isolation: |
|
1.500 Vac |
Input: |
|
Nr 2 isolated and independent channels, current 0..20, 4..20 mA; voltage 0..5, 1..5, 0..10, 2..10 V |
Output: |
|
Current 0..20, 4..20 mA; voltage 0..5, 1..5, 0..10, 2..10 V |
Accuracy: |
|