Pulse converters:
Pulse converters allow to treat impulsive signals coming from devices that provide frequency measurement, pulse acquisition, metering, counting, speed, batch production or waste etc. The acquisition and transmission are carried out by measuring the period or frequency of pulse signals from industrial sensors such as photoelectric sensors, proximity switches, encoders, reed etc
|
|
EZ104: |
|
DC to frequency isolator / converter |
EZ111: |
|
Frequency to DC isolator / converter |
EZ104
DC to frequency isolator / converter
EZ104 allows a conversion of the current or voltage input signal into a series of pulses with constant duration. A typical use is when, with a flow meter featuring an analogue output (example 4-20mA), the flow must be totalized. the output is programmable in a range from 1 pulse every 2 hours to 10 KHz. A 3-way galvanic isolation among Power supply // input // output circuits assures the integrity of your datas.
Order code : |
|
EZ104 |
Description: |
|
DC to frequency isolator / converter |
Power supply: |
|
19..40 (9..30 option) Vdc, 19..28 Vac |
Isolation: |
|
1.500 Vac |
Input: |
|
Current 0..20, 4..20 mA; voltage 0..5, 1..5, 0..10, 2..10 Vdc |
Output: |
|
Transistor npn open collector 30 Vdc 300 mA; reed relay30 Vdc/ac 100 mA, max frequency 10 kHz |
Accuracy: |
|
0,2% |
EZ111
Frequency to DC isolator / converter
EZ111 allows a conversion of a frequency signal and provides a mA/V standard output signal. The input is programmable in a range from 1 mHz to 9,99 KHz. It’s completely configurable through dip switches. A 3-way galvanic isolation among Power supply // input // output circuits assures the integrity of your datas.
Order code : |
|
EZ111 |
Description: |
|
Frequency to DC isolator / converter |
Pulse Input: |
|
contact, npn 2 / 3 wiresi, pnp 3 wires 24 Vdc supply, namur, photoelectric, Hall sensor, variable reluctance, 24 V pulse, TTL, oval wheel counter flow meters |
Frequency: |
|
From 1 mHz (0,001 Hz) to 9.99 KHz |
Settable full scale: |
|
From 10 mHz (0,01 Hz) to 9.99 KHz |
Output: |
|
Current 0..20, 4..20 mA; voltage 0..5/10, 1..5, 2..10 V |
Power Supply: |
|
19..40 (9..30 opz.) Vdc, 19..28 Vac |
Isolation: |
|
1.500 Vac |
Conformity: |
|
CE, UL-UR CSA |