The Isolation Amplifier DEN 240M is used for isolation and conversion of 0 ... 20 mA, 4 ... 20 mA and 0 ... 10 V standard signals.
The Isolation Amplifier DN 240M is used for isolation and conversion of 0 ... 20 mA, 4 ... 20 mA and 0 ... 10 V standard signals.
Its high level of reliability and cost optimized design make the DN 240M the first choice in customer applications.
Unique in its price class, the DN 240M provides application flexibility thanks to the calibrated range.
The desired input and output range can be easily set by terminal pins and due to the calibrated range selection no further adjustment is necessary.
The flat module with 15.5 mm height for pcb assembling saves space in the customer application.
Input signal |
0...20 mA, 4...20 mA, 0...10 V terminal selectable |
|
Input resistance |
Current input Voltage input |
22 Ohm 1 MOhm |
Overload |
Current input Voltage input |
≤ 100 mA Voltage limitation via 30 V Z-Diode, max. continuous current 30 mA |
Output signal |
0...20 mA, 4...20 mA, 0...10 V, terminal selectable |
|
Load |
Current output Voltage output |
≤ 10 V (500 Ohm @ 20 mA) ≤ 10 mA (1 kOhm @ 10 V) |
Offset | 20 µA / 10 mV | |
Ripple | < 20 mVrms |
Transmission error | 0.3 % of measured value | |
Temperature coefficient 1) | 150 ppm/K of final value | |
Cut-off frequency (-3 dB) | Approx. 1 kHz | |
Test voltage |
2.5 kV, 50 Hz Input against output against power supply |
|
Working voltage 2) (Basic Insulation) |
Up to 600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 between all circuits. | |
Ambient temperature |
Operation Transport and storage |
–10 °C to +60 °C –20 °C to +80 °C |
Power supply | 24 V DC ±10 % | DC approx. 1,2 W |
EMC 3) | EN 61326 -1 | |
Construction | Module for pcb assembling, 52.5 x 36 x 15.5 mm (l x w x h) | |
Weight | Approx. 60 g |
Device | Order No. | ||
Isolation Amplifier Module, calibrated range selection | DEN 240M |